GUARD
For mechanical protection of waterproofing
Explore GUARD 8, GUARD 8+ and GUARD HP where a protective layer is needed between backfill and waterproofing.
View GUARD series and specificationsPROJECT ASSISTANT / FOUNDATION AND BASEMENT WALLS
Enter the foundation depth and groundwater level to view approximate soil and water pressures with depth.
Enter both depths measured downwards from the external ground surface.
To the bottom of the wall in contact with soil.
For example, 2 m: water is 2 m below ground level.
0 m: water at ground level.
H and d are measured downwards from the same external ground level. d is not the water height measured upwards from the wall base.
Factored pressure = total pressure × 1.50.
View assumptions and scope
Enter valid depths to display the pressure summary and table.
03 / PRODUCT FAMILY GUIDE
Pressure is one input to product selection.
The required function is also decisive.
For mechanical protection of waterproofing
Explore GUARD 8, GUARD 8+ and GUARD HP where a protective layer is needed between backfill and waterproofing.
View GUARD series and specificationsFor filtration and water removal
Explore FLOW 8, FLOW 8+ and FLOW 10+ geocomposite drainage series where water must be filtered and conveyed to the outlet.
View FLOW series and specificationsThe calculation estimates lateral pressure assuming homogeneous backfill and hydrostatic water. It does not recommend a product class automatically. Long-term compression behaviour and flow capacity under load require data appropriate to the project detail.
Rainwater drainage calculation →CALCULATION BASIS
These values are fixed assumptions of this tool, not a regulatory standard or an upper limit for every soil.
z is the calculation depth; d is groundwater depth below the surface. Thickness above water a = min(z, d); thickness below water b = max(0, z − d).
Soil: K₀ × [γ × a + (γsat − γw) × b]
Water: γw × b
Total: soil + water
Factored pressure: total × 1.50
1.50 is a fixed factor chosen for this preliminary estimate; it does not replace project load, safety or material factors. Short-term compressive strength cannot be used as a long-term allowable load.
When no groundwater is selected, b = 0. The tool accepts positive wall depths up to 100 m; this range does not imply engineering suitability.
Earthquakes, surface surcharges, backfill compaction, swelling, layered soils, flowing water and uplift beneath the foundation are excluded. K₀ may exceed 1 in some soils. A drainage sheet alone does not prove that water pressure is eliminated.
Method source: FHWA, Soils and Foundations, Chapter 10